NEW METHODOLOGY FOR LIFETIME EVALUATION OF MEDIUM AND SMALL SIZED POWER TRANSFORMER

郭永基
DOI: https://doi.org/10.3321/j.issn:1000-1026.2001.21.010
2001-01-01
Abstract:Based on the detected degree of polymerization (DP) value of insulation paper on power transformer, a new formula to describe the relationship between DP and the lifetime of power transformer is deduced, and a new methodology for evaluating the lifetime of power transformer during design and manufacture stages is presented. Experiments on detecting DP of the insulation paper are designed. By using the proposed methodology, lifetime of SBS9 transformer is evaluated by 22.28 years. The probability that the lifetime of transformer is larger than 19.15 years is 90%. The new methodology may be used in manufacture factories of transformers and power supply corporations.
What problem does this paper attempt to address?