Measurement principle of tuned balance method for partial discharge

Gang Liu,Demin Tu
1998-01-01
Abstract:Input circuit of traditional balance method for partial discharge (PD) measurement is a parallel circuit of resistance and capacitance. There are many disadvantages with this measuring circuit and it is difficult to extend its use in HV and UHV domain. The measurement principle of tuned balance method with input circuits of inductance and capacitance for PD detection is analyzed. It is shown by simulated test that under the fixed center frequency of measurement the innumerable balance points exist in adjustable range of tuned capacitors, the capacitance ratio of sample to reference capacitor can reach to 100, and the inhibitory ratio of interference is up to 2000-4000. It is shown by relevant test results in practical HV circuit that the inhibitory ratio of interference is from 1950 to 600 in ratio range of capacitance of samples to that of reference capacitor from 1 to 1000, and the minimal detective PD is from 0.1 PC to 0.6 pC.