PRINCIPLE OF SELECTIVE FREQUENCY BALANCE METHOD FOR PD MEASURING

LIU Gang,TU Demin
DOI: https://doi.org/10.3969/j.issn.1003-3076.1999.02.004
1999-01-01
Abstract:Input circuit of traditional balance method for partial discharge (PD) measurement consists of two parallel circuits of resistance and capacitance.There are many disadvantages with this measuring circuit and it is difficult to spread its use in HV and UHV domain.The measurement principle of selective frequency balance method with input circuits of inductance and capacitance for PD detection is analyzed in detail in this paper.Simulated test shows that under the fixed center frequency of measurement,the innumerable balance points exist in adjustable range of tuned capacitors.The pivotal part of selective frequency balance method for PD is the use of narrow wide band filter and amplifier (NWBFA).Practical HV test shows that the minimum acceptable discharge magnitude is 0.06pC when the sample's capacitance in 255pF.Under the condition of very heavy interference signals.