Measurement of power system dynamic frequency when signal amplitude changes

Yong Min,Renjie Ding,Weihua Xiong,Yingduo Han
1997-01-01
Abstract:This paper discusses the effect that signal amplitude changes have on the results of frequency measurement in power systems, advances the concept of signal's apparent frequency based on the analysis of the basic assumption of different frequency measurement approaches, proves that the apparent frequency is the superposition of actual signal frequency and some high frequency components (close to twice the normal frequency, about 100Hz in 50Hz systems), and frequency measurement approaches can not get the actual frequency directly. Instead of that, the results of approaches are more similar to the apparent frequency and also contains some high frequency components. The paper then provides an approach to derive the actual signal frequency from the measured frequency and gives a simple example.