Asymmetric Short-circuit Current Calculation for Inverter Interfaced Distributed Generators With Negative Sequence Current Injection Integrated in Power Systems

ZHOU Niancheng,YE Ling,WANG Qianggang,XIE Kaigui
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2013.36.010
2013-01-01
Abstract:The fault current of the inverter interfaced distributed generator (IIDG) is determined by its control strategy under the grid fault condition. However, the traditional short-circuit calculation of power systems with IIDG has not considered the effect of its negative sequence current and causes limitations on it. The short-circuit calculation principle for power grid with IIDG was analyzed. According to the sequence currents control and the reactive power support of IIDG during the fault, the current source model based on symmetrical components of IIDG was established for short-circuit current calculation. The current and terminal voltage responses of inverter interfaced distributed generators (IIDGs) under different control conditions were compared to investigate the relationship of the short-circuit currents with power system and the ride through time. Finally, an iterative algorithm considered the ride through time and the sequence current control to determine the sequence components of short-circuit current for multiple IIDGs in power system was proposed. The correctness of proposed method is verified by PSCAD/EMTDC simulation software.