Wind-induced weak parts and reinforcement methods of long cross-armed transmission tower

楼文娟,姜雄,夏亮,金晓华,王振华
DOI: https://doi.org/10.3785/j.issn.1008-973X.2013.10.015
2013-01-01
Abstract:A fine aero-elastic model of 220kV long cross-armed angle steel transmission tower was designed and produced to investigate wind-induced response under terrain B wind field. Structural optimization for wind resistant design of the tower was conducted by means of the numerical analysis and the phenomena of the wind tunnel test. Essential conclusions are as follows: due to the gas-solid coupled effect, strong flexure-torsion vibration was observed during the wind tunnel test, which would lead to the premature instability of angle steel members. Several local vibrations appeared in the very first several modes subjected to the fluctuating wind excitation, which resulted in the large out-of-plane deformation and eventually the reduction of the ultimate bearing capacity. Further research shows that the torsional vibration can be apparently reduced by increasing the rigidity of diagonal bracings between the arms of the tower. Adding diaphragms with appropriate arrangements can remarkably optimize the dynamic characteristics, suppress the local vibrations, and ensure the global stability of the tower.