Active Damping Method Based on Bi-Quad Filter for Microgrid Applications

Lu Xiaonan Sun Kai,Huang Lipei,Lipei Huang
DOI: https://doi.org/10.3969/j.issn.1000-6753.2013.03.037
2013-01-01
Abstract:The power electronics interfacing converters are usually parallel connected to the common bus via LCL filters in a microgrid. The LCL filters have resonance problems. Especially in a parallel inverter system, the additional resonance and anti-resonance peaks can be found in the frequency domain analysis result. In this paper, the frequency domain characteristic of the parallel LCL-filtered inverters is analyzed. Active damping method based on bi-quad filter is reached. By using this kind of method, the multiple poles leading to instability issues are damped at the same time without additional sensors and close-loops in the control system. The additional two pairs of zeros and poles are involved by the bi-quad filter. Hence, the original root locus is changed and the multiple pairs of unstable poles are moved into the unit circle in z domain. The system stability is thereby guaranteed. The theoretical analysis is showed by the model with three LCL filtered parallel inverters implemented in dSPACE1103.