Research on DC Magnetic Biasing Characteristic of Converter Transformer for AC/DC Corridor-Sharing Power Transmission System

ZHANG Longwei,WU Guangning,FAN Jianbin,HUANG Bo,ZHU Jun
DOI: https://doi.org/10.13335/j.1000-3673.pst.2013.12.019
2013-01-01
Abstract:In view of complex composition of DC magnetic biasing in converter transformer for AC/DC corridor-sharing power transmission system, it is of significance for stable operation of the transmission system to correctly analyze its constituents. A DC magnetic biasing model for converter transformer and a transmission line model of AC/DC corridor-sharing power transmission system are built, and the DC quantities due to ground potential of the soil and power frequency induction of AC/DC transmission line are calculated respectively; the influencing rule of parallelly erected lengths of AC/DC transmission lines and the approach distance between the centers of AC and DC transmission towers on DC magnetic biasing in converter transformer is researched. Research results show that the longer the parallelly erected lengths of AC/DC transmission lines, the larger the DC magnetic biasing in converter transformer is, and the higher proportion of DC magnetic biasing due to power frequency induction in the total DC biasing, the lighter impact of ground potential of the soil on this proportion will be; the farther the approach distance between the centers of AC and DC transmission towers, the lower the DC magnetic biasing in converter transformer will be, and the smaller the proportion of DC magnetic biasing component due to power frequency induction in total DC magnetic biasing, the stronger impact of ground potential of the soil on this proportion will be.