Economic and safe operation of parallel transformer considering hottest-spot temperature

Liuhui Zhu,Gehao Sheng,Wanjian Bai,Jing Chen,Yadong Liu,Ronghua Cui,Xiuchen Jiang
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.10.017
2013-01-01
Abstract:An operating strategy considering the real-time variation of hottest-spot temperature is proposed to ensure the safety of parallel power transformer during overload operation. The daily load curve is divided into high-load period and low-load period according to the actual load variation. During the high-load period, both the minimum power loss of economic operation and the temperature rise of transformer hottest-spot should be considered, by which, the economic operating mode and the switching time of parallel power transformers can be determined. It applies the finite difference method to estimate the hottest-spot temperature according to the load curve and ambient temperature and adopts the binary searching method to obtain the optimal switching time. Analysis of two three-winding transformers with different capacities and running in parallel shows that, the proposed strategy ensures the safe operation of transformers as well as reduces the transformer loss.
What problem does this paper attempt to address?