Abstract:In the traditional transformer temperature calculation methods, the hot spot temperature (HST) is obtained by calculating the oil temperature rise, winding temperature rise, and then adding the ambient temperature. However, there is a gap between the HST calculated by this method and the measured temperature. There are two reasons for this phenomenon, the influence of environmental factors on the internal temperature of transformer has delay effect, and the influence of multiple environmental factors is not considered. By making corresponding improvements in these two aspects, an improved transformer HST calculation method is proposed. By comparing the calculated temperature of the improved method with the measured temperature, it is concluded that the internal temperature of the transformer can be well fitted by the proposed method. Through the comparative analysis with the traditional method, it is found that the calculation accuracy has been greatly improved. By analyzing the working data of transformers in different regions, different seasons and different operating years, the influence of multiple environmental factors on the temperature calculation and its change trend are summarized, and the effectiveness of this method is verified.