Research on optimized phase sequence arrangements for 500 kV quadruple-circuit transmission line on the same tower
ZHANG Xiao,ZHOU Hao,ZHAO Bin-cai,Chen Jia-mao
DOI: https://doi.org/10.3969/j.issn.1004-9649.2010.02.010
2010-01-01
Abstract:There are 1 296(64)phase sequence arrangements for quadruple-circuit transmission lines on the same tower theoretically.In order to obtain the optimal arrangement,taking 500 kV quadruple-circuit transmission lines on the same tower as an example,the electric characteristic of transmission line including electromagnetic environment,natural power,imbalance transposition,etc under every phase sequence arrangement were compared and analyzed by method of exhaustion.The result shows that the arrangement has a certain impact on the electric characteristic of transmission line.Power frequency magnetic field,radio interference and audible noise are not the decisive factors to optimal phase sequence arrangement.By taking electromagnetic environment,natural power,imbalance transposition,etc into account and using sorting method,the optimal arrangement for 500 kV quadruple-circuit transmission lines on the same tower is obtained,which is 1616 for tower d and 1462 for tower e.Finally typical arrangements for quadruple-circuit transmission lines on the same tower are recommended.The calculation method and results be referred to for projects.