Effect of Sulphate Concentration Change on Iron Release in Drinking Water Distribution Systems

米子龙,张晓健,陆品品,陈超,汪隽,顾军农
DOI: https://doi.org/10.16511/j.cnki.qhdxxb.2013.05.025
2013-01-01
Abstract:This study investigated the effect of sulphate concentration changes on the iron release in a drinking water distribution system caused frequently switching of the water source.The rates of iron release from corrosion scale for different water sources were analyzed with pipe section reactors designed to simulate the distribution system flow mode.The results showed that the sulphate concentration was the dominant factor that led to red water.The iron release rate from the corrosion scale correlated well with the sulphate concentration with a sulphate concentration increase from 25mg / L to 180mg / L accompanied by a Larson ratio increase from about 0.35to 1.40.The turbidity in the pipe section reactors increased 6NTU after 8h,the color increased 50degrees and the iron release rate increased 2.00mg /(m 2.h).These results indicate that the sulphate concentration should be lower than 75mg / L and the Larson Ratio should be controlled to less than 0.70for the water quality in the distribution system to meet the Chinese drinking water quality standard.Based on these results,t was suggested to be and controlled less than 0.70in order that in meet the standard of drinking in China.
What problem does this paper attempt to address?