Control Effect of Regulating Ph and Alkalinity on Iron Release in Drinking Water Distribution System

Zi-long MI,Xiao-jian ZHANG,Yang WANG,Chao CHEN,Jun-nong GU
DOI: https://doi.org/10.3969/j.issn.1000-4602.2012.13.010
2012-01-01
Abstract:The control effect of regulating pH and alkalinity on iron release in the drinking water distribution system was investigated.Experiments using the pipe section simulation reactor found that the iron release rate,turbidity and color decreased significantly with increasing pH and alkalinity.Specifically,after increasing pH from 7.6 to 8.2 for 15 d,the iron release rate,turbidity and color decreased by 47%,54% and 46%,respectively.Meanwhile,increasing alkalinity from 135 mg/L to 260 mg/L(calculated as CaCO3) for 15 d,the iron release rate,turbidity and color decreased by 50%,58% and 52%,respectively.The cost-effectiveness of regulating pH and alkalinity to control iron release in drinking water was evaluated.The results showed that the cost of regulating pH of finished water was appropriate.This method can be used as an emergency water treatment technology for red water control.
What problem does this paper attempt to address?