Analysis of Resistance Disturbance Capability of Optical Current Transformers

Wen-bin YU,Guo-qing ZHANG,Zhong-feng LU,Gui-zhong WANG,Zhi-zhong GUO
DOI: https://doi.org/10.3969/j.issn.1674-3415.2012.12.002
2012-01-01
Abstract:The closed light path structure and the straight through light path structure are the two primary structures of optical current transformers based on Faraday magnetic-optic glass. The advantages of optical current transformers based on the straight through light path structure are obvious on the machining difficulty and the stability. But the disadvantages are also obvious on the conductor positional sensitivity and the resistance disturbance capability. In this paper, the differential optical current transformer is proposed. The influence of the conductor positional change and the magnetic crosstalk on the measurement precision is analyzed. The results show that the differential optical current transformer used in smart substation with phase spacing more than 0.8 m can absolutely achieve the measurement precision of 0.2-level without special shield.