Fault Location Method for Double-circuit HVDC Transmission Lines on Same Tower Based on Single-circuit Electrical Quantities
LI Haifeng,QIUYingdan,GUOLüxing,WUJiyang,LIANGYuansheng,WANGGang
DOI: https://doi.org/10.7500/AEPS20151107004
2016-01-01
Abstract:There exists complicated electromagnetic coupling between different polar lines for double-circuit high-voltage direct current(HVDC)transmission lines on the same tower.In an actual project,the control and protection of each circuit is still based on the single-circuit electrical quantities.Inevitably,it is unable to achieve its complete decoupling,which increases the difficulty in accurate fault location.Firstly,the characteristics of the modulus based on single-circuit quantities are analyzed using the transformation matrix.Based on this,the new differential-mode component,which has eliminated the influence of the earth-mode,is constructed.The characteristics and parameter selection of the new differential-mode component are also given.Then,given the characteristic that the voltage distributions of the non-fault point calculated by the voltage and current measured in both terminals have the largest difference around the fault time,the maximum voltage difference zone of the non-fault point is defined.Further,a fault location method based on single-circuit quantities is proposed.The PSCAD/EMTDC simulation model of real double-circuit HVDC transmission lines on the same tower is constructed with extensive simulation results showing that the proposed method is not only highly accurate,but also unaffected by fault polar lines,fault position and the resistance.