Application of Load Monitoring System in Disposing Fault of Distribution Network

武鹏,徐群,沈忠旗,程浩忠
2012-01-01
Abstract:According to the variation of the three-phase voltage data gathered in real time from the load monitoring system,the location of some faults in the distribution network can be analyzed and judged.When single-phase disconnection fault occurs,the address of disconnection can also be judged according to the voltage waves of two adjacent load monitoring devices.Also the disconnection phase can be ascertained by combining the connection mode of the distribution transformer.For the case where the transformer inner fault happens and the breaker in substation trips then auto-reclose acts successfully,the reason and location of the fault transformer can be judged according to the presence or absence of voltage data from the load monitoring device.It can be seen from the process of handling the actual fault in the distribution network of Songjiang district,the validity and effectiveness of the load monitoring system in coping with the single-phase disconnection fault is obvious.
What problem does this paper attempt to address?