Analysis of Leakages of Plate Evaporative Air Cooler and Prevention

Wu Fei,Bai Wenjun,Feng Jiangang,Niu Yanhong,Han Jinsheng
DOI: https://doi.org/10.3969/j.issn.1007-015X.2009.01.005
2009-01-01
Abstract:As compared with surface evaporative air cooler,the plate evaporative air cooler offers advantages of greater cooling duty, higher heat transfer efficiency,lower power consumption and lower pressure drop etc.It is very applicable for clean medium cooling and installation with very limited floor space.In May 2005,two plate evaporative air coolers were installed in the LPG fractionation unit of PetroChina Karamay Petrochemical Company.The two coolers were soon discarded because of frequent leakages of plate tube. The investigation found that the culprits of leaking are off-specification of chlorine ion in cooling water tank(over 300 mg/L) and residue stress of plate tube.The protective measures are:strengthening quality management of cooling water in water tank,strictly following the specifications on equipment welding and post weld heat treatment and implementation of effective process operation procedures,etc.
What problem does this paper attempt to address?