Measurement of Internal Pressure of Vacuum Tubes by Micro-Discharge and Emission Current

Zhao Ziyu,Dan Shuheng,Jiang Xiuchen,Ma Naixiang,Luo Liwen,Song Huansheng,Liu Chongfang
DOI: https://doi.org/10.1109/deiv.2008.4676739
2008-01-01
Abstract:The traditional methods for measuring internal pressure P of vacuum tubes of breakers are the magnetron and power frequency voltage withstand test. A magnet coil is needed by magnetron and only very bad tubes can be picked out by voltage withstand test. In this paper, a new method-inception voltage V-d of micro-discharge / inception voltage V-o of emission current, i.e. V-d/V-o method, is presented. It is found that by means of the relationship V-d/V-o similar to P, Internal pressure P can be measured accurately although vacuum gap d vary from 0.2mm similar to 0.3mm. By this new method, internal pressure of vacuum tubes can be measured without using magnetic coil, but with following process: firstly, when contacts is under closed situation, by screwing the nut to stretch compression spring, vacuum gap 0.2mm similar to 0.3mm Is obtained, secondly power frequency voltage is applied to the gap and gas adsorption layers are polished by micro-discharge current, finally the V-d and V-e of the vacuum tube is measured. Theoretical study show that the bigger the V-d/V-o. Is, the smaller the P is. So by measuring the value of V-d/V-o. the value of P can be obtained. The relationships of V-d,V-e,V-d/V-o. with P were measured in laboratory, the test results show that the measuring ranges of P can be 10(0)Pa similar to 10(-3)Pa by this new method.