Monitoring principle and methodology for air change flow in indoor air

Zhang Guangshan,Bai Yuhua,Liu Zhaorong,Li Jinlong
DOI: https://doi.org/10.3969/j.issn.1001-3865.2005.08.021
2005-01-01
Abstract:Air change flow is one of the sanitarian standards which can evaluate indoor environmental quality,and it is also one of the important parameters that may calculate gas discharge amount per unit time.This experiment uses carbon dioxide as the tracer gas,which comes from dry ice sublimation or human breathing,to examine air change flow of indoor and in-vehicle microenvironent.For human breathing,the indoor air change flow is calculated by using derivation formulae(steady-state method,analytic solution and difference method) from box model. Preliminary results indicate that air change flow,which is calculated by analytic solution and difference method,has no significant statistical difference without people inside microenvironment.When human breathing impact must be considered with people inside microenvironment,all the derivation formulae could be used to calculate air change flow.In this case the results are credible and the accuracy is high.Using carbon dioxide from human breathing as the tracer gas,the difference method is not ideal and the result windage is high,while the steaty-state method is credible and the reproductivity is good.
What problem does this paper attempt to address?