A new PM2.5-based CADR method to measure air infiltration rate of buildings

Cong Liu,Siyu Ji,Fengjiao Zhou,Qingbin Lin,Yiqi Chen,Xiaoliang Shao
DOI: https://doi.org/10.1007/s12273-020-0676-4
IF: 4.0083
2020-07-17
Building Simulation
Abstract:<p class="a-plus-plus">Air infiltration is an important way to exchange indoor air with outdoors. It significantly impacts energy consumption and air quality of buildings. Fine particles (PM<sub class="a-plus-plus">2.5</sub>) in the outdoor atmosphere environment are a potential natural tracer for the measurement of air infiltration rate, especially in the long term field measurement. In this study, a PM<sub class="a-plus-plus">2.5</sub>-based method, named as CADR (clean air delivery rate) method, is developed to supplement traditional tracer gas method in order to make routine measurement in realistic environments possible and convenient. An air cleaner is installed indoors to reduce indoor PM<sub class="a-plus-plus">2.5</sub> concentration. Air infiltration is determined by fitting a model to the decreasing concentration data. Comparison with CO<sub class="a-plus-plus">2</sub> decay method in four different indoor environments gives a normalized mean error of 19% and a correlation coefficient of 0.80 for this method. This justifies the CADR method as a feasible option to measure air infiltration rate. Although subject to several constraints, the proposed method would facilitate field measurement under realistic conditions by being combined with current tracer gas methods.</p>
thermodynamics,construction & building technology
What problem does this paper attempt to address?