Numerical simulation on installation location of combined air cleaners in underground stores

Shao Xiaoliang,Han Zongwei,Shi Wenxing
DOI: https://doi.org/10.3969/j.issn.1002-8501.2010.10.001
2010-01-01
Abstract:Studies five typical pollution states and coexistence of two contaminants in underground stores by numerical simulation to find the optimal location for combined air cleaners.The result shows that the combined air cleaners should be installed in different places under different pollution conditions.In most cases,the optimal location is on the return air duct of air conditioning system with primary return air,but when pollution is serious in local area,the location adjacent to contaminant sources or both adjacent to contaminants and on return air duct is appropriate.When combined air cleaner is located near the contaminant sources,the installation position should be determined according to releasing intensity and concentration limits of contaminants existed at the same time.