Technique of Cleaning by Water Vapor for Live Power Equipment

王志龙,张晋,李荣立,汲胜昌
DOI: https://doi.org/10.3969/j.issn.1009-9239.2009.03.018
2009-01-01
Abstract:A technique called cleaning by water vapor for live power equipment was investigated.The effects of cleaning by water vapor were tested through application of cleaning by water vapor in a power-off lightning arrester with composite external insulation.The flashover voltage of polluted insulator strings wetted by water vapor was measured.The curve of flashover voltage of 35 kV insulator strings versus equivalent salt deposit density(ESDD) was drawn.
What problem does this paper attempt to address?