Ignition characteristics of commonly used exterior thermal insulation systems with rigid polyurethane foam

QI Yan-jun,CHENG Xu-dong,XU Lei,ZHANG He-ping
2012-01-01
Fire Safety Science
Abstract:The ignition characteristics of rigid polyurethane foam based exterior thermal insulation systems was experimentally studied by the cone calorimeter.The four types of systems examined in this paper include the thin-plastering exterior insulation system(thin-plastering system),the exterior thermal insulation system with ceramic tile face(ceramic face system),the composited exterior wall thermal insulation system with mineral binder and expanded polystyrene granule aggregate(mineral binder composited system),and the decorative insulated exterior wall panel system(decorative panel system).The experimental results show that the ignitions of both the rigid polyurethane foam board and the rigid polyurethane foam based exterior insulation systems can be described by the thermal-thick ignition model.The protective layer of the mineral binder composited system has the best delay effect on the ignition time.The time-delay effect of protective layer of the ceramic face system is slightly worse than the mineral binder composited system but is much better than the 5mm and the 3mm thin-plastering system.The decorative panel system has the worst time-delay effect on the ignition.
What problem does this paper attempt to address?