Comparison of Diffluence Performance for Distributors with Different Structures

GAO Jing-dan,DING Guo-liang,HU Hai-tao,GAO Yi-feng,SONG Ji
DOI: https://doi.org/10.3969/j.issn.2095-4468.2013.03.106
2013-01-01
Abstract:The liquid flow rate at the outlet of jack-type distributor,cone-type distributor and reflect-type distributor was measured under test conditions of different air/water flow rates and different installation angles,and the influences of two-phase flow rate and installation angle on diffluence performance were analyzed.For the jack-type distributor,the diffluence performance is greatly affected by the installation angle.When the jack-type distributor is installed vertically,the diffluence performance reaches the best,and it becomes worse as the flow rate increases,which means jack-type distributor is suitable for air conditioner with low refrigerant flow rate.For the cone-type distributor,diffluence performance is little affected by the installation angle,and it reaches the best when the installation angle is 30°.The performance becomes better as the flow rate increases,which means cone-type distributor is suitable for air conditioner with high refrigerant flow rate.For the reflect-type distributor,diffluence performance is little affected by the installation angle,and the performance becomes worse as the flow rate increases under the condition of oblique installation,which means reflect-type distributor is suitable for air conditioner with low refrigerant flow rate.