Experimental Investigation of Performance of Jace-Type Distributor

GAO Jing-dan,DING Guo-liang,CHEN Guo-sheng,GAO Yi-feng,SONG Ji
DOI: https://doi.org/10.3969/j.issn.2095-4468.2013.02.102
2013-01-01
Abstract:The liquid flow rate of each outlet of jack-type distributor is measured under test conditions of different air/water flow rates and different installation angles to know the influence of two-phase flow rate and installation angle on the performance of distributor. From the experimental results, it can be known that, the performance becomes better as the two-phase flow rate increases; the performance gets the best when it is vertically installed; the performance gets worse when it is inclined installed. When the installation angle is between 0°~30°, the unevenness increases gradually as installation angle increases; while when the installation angle is between 30°~90°, the increase rate of unevenness becomes bigger as installation angle increases.