Abstract:The reactor with HYBASTM technology(Anoxkaldnes) was adopted to treat heavily polluted river water in city — Buji river water in Shenzhen.The reactor continuously run more than eight months,covering three seasons of winter,spring and summer.The results show that ammonia nitrogen in effluent was from 0.1 to 4.6mg·L-1 with the average of 1.2mg·L-1,meeting the requirement of the Grade One(A) of Discharge Standards for Municipal Wastewater Treatment Plant(GB 18918—2002) under the condition with 11h of hydraulic retention time(HRT),11d of sludge retention time(SRT),200% to 400% of internal reflux ratio,and 75% of sludge reflux ratio.Ammonia nitrogen in effluent was lower than 0.5mg·L-1 with over 20℃.HYBASTM technology had a high removal capacity for ammonia nitrogen.Many factors,such as HYBASTM technology belonging to pre-denitrification process etc.,caused the abundance of NO3-—N in effluent,further resulting in the low removal efficiency of TN.Adding methanol as external carbon improved removal efficiency of TN.COD,suspended solids and total phosphorus in effluent met the requirements of the Grade Two or the Grade Three of Discharge Standards for Municipal Wastewater Treatment Plant(GB 18918—2002).Another physical-chemistry technologies should be followed to improve the quality of effluent.HYBASTM reactor recovered to the former removal ability in a short time after a period of stopping run.