Application of the Pilot Impedance to the Single Power Supply Transmission Lines

Jing-de XIA,Jia-le SUONAN,Shu-ping GAO,Shi-en HE,Kai LIU,Li WANG
DOI: https://doi.org/10.3969/j.issn.1674-3415.2012.09.006
2012-01-01
Abstract:We modify the correlative phasor relationship of the pilot impedance electrical data and adjust the opreation threshold of fault identification of transmission line pilot protection to extend and may meet the running environment of the transmission lines based on the single power supply,through systematically analyzing the impedance value difference of the transmission line pilot impedance based on single power supple and double power supply and completely reserving the original derived result of the pilot impedance.This computational method adopts the power frequency fault components as the calculating electrical quantities of the pilot impedance,under the condition of compensating power frequency line capacitances,it may be determined that the internal fault occurs when the impedance amplitude is smaller than the setting value,conversely,it can be judged non-fault occurring in the protected region.This algorithm can effectively improve the performance of the transmission line pilot protection under the single power supply.In EMTP simulation,we establish the transmission line simulation model of single power supply of a 1000 kV 500 km,and execute simulation verifications based on each fault.The simulation results indicate that this computational method has enough stability and sufficient reliability in the single power supply environment.
What problem does this paper attempt to address?