Improved pilot protection based on longitudinal impedance of decoupled transmission line

Jingde Xia,Jiale Le Suonan,Yining Zhang,Bin Wang,Wenquan Shao,ShiEn He
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.12.010
2013-01-01
Abstract:Based on the LI(Longitudinal Impedance) characteristic of single-phase model, an accurate decoupling algorithm of LI for three-phase model is proposed, which ensures its theoretical reliability. An improved pilot protection applying the LI of fault component is thus proposed for transmission line. When external fault occurs, its LI is equal to the positive-sequence impedance of line; when internal fault occurs, it is equal to the negative phasor sum of the positive-sequence impedances of equivalent system. The proposed protection scheme has sensitive operation and reliable performance, avoiding the synchronous sampling of electrical variables at each terminal of line. The composite influence of system impedance and line capacitance on LI is analyzed and an auxiliary criterion is added, which makes the proposed protection scheme suitable for various operational environments. Simulative results show its correctness.