Transmission Line Pilot Protection Principle of Fault Total Content Based on Composite Impedance of Individual Phase

索南加乐,夏经德,焦在滨,王莉,何世恩,刘凯
2010-01-01
Abstract:A transmission line pilot protection principle based on the composite impedance of individual phase is proposed.The individual phase impedances are calculated from the fault total content differences of the voltages and currents at both terminals of the line,and then used for judging if the fault is occurs at the line.If the fault is outside of the protected area,the individual phase impedances just equal to the positive sequence impedance of whole length of the transmission line,while they will obviously differ from the determined value in case of the fault inside of the protected area,which refers an amplitude criterion.The proposed protection with independent phase selection possesses identity of reliable performance,sensitive operation,and strong adaptation.The EMTP simulation and the dynamic simulation test results indicate the effectiveness of the presented principle.
What problem does this paper attempt to address?