Calculation of local resistance coefficient of ball valve in water supply network

He Zhonghua,Yuan Yixing,Qiu Wei
DOI: https://doi.org/10.3969/j.issn.1673-9353.2012.04.007
2012-01-01
Abstract:In order to determine the local resistance coefficient of valves in water supply network,a method of establishing local resistance coefficient formula was proposed based on the geometric calculation and field experiments.At first,the relationship between flow area of ball valve and rotation angle of spool was built by geometric calculation.The area opening degree of ball valve was defined as the ratio between flow area at a rotation angle and flow area in the fully open condition.The defect of traditional definition about the ratio between spool rotation angle and rotation angle in whole process as ball valve opening degree was put forward.Taking ball valves with the diameter of DN20 as the experimental object,the pressure differences and flow values at different opening degrees were collected and the relative local resistance coefficients were calculated by field experiments.The relationship between area opening degrees and local resistance coefficient of ball valves was established by curve fitting method.Another experimental data of area opening degree and local resistance coefficient of ball valves indicated that this calculation formula could be applied effectively in the calculation of ball valves local resistance coefficient.
What problem does this paper attempt to address?