Treatment of Wastewater Containing Cr6+ by High Voltage Pulsed Electrocoagulation

朱小梅,孙冰,赵娜,那海珍
DOI: https://doi.org/10.3969/j.issn.1000-1565.2010.05.021
2007-01-01
Abstract:High voltage pulsed electrocoagulation technology was designed to remove the total Cr,Cr(Ⅵ) and Zn(Ⅱ) of electroplating wastewater by using iron plate as electrode in the hydroelectric bath,and the method was compared with the direct current electrocoagulation method.The initial mass concentrations of the wastewater are total ρ(Cr)= 168.6 mg/L,ρ(Cr(Ⅵ)) = 22.8 mg/L and ρ(Zn(Ⅱ)) = 29.9 mg/L.Experimental results indicate that the high voltage pulsed electrocoagulation technology can remove the electroplating wastewater efficiently.After adjusting the pH to 7-9 by NaOH,the residual metal mass concentrations of the wastewater under legal limits of industrial water(GB 8978-1996) are obtained,just after about 8 minute.The total Cr mass concentration is about 0.1 mg/L,Cr(Ⅵ) mass concentration is also about 0.1 mg/L,Zn(Ⅱ) mass concentration is about 0.6 mg/L with the optimum experimental conditions.Compared to the direct current electrocoagulation method and conventional existing techniques,the high voltage pulsed electrocoagulation technology has the merits of easier operating,shorter running time and higher energy efficiency.The high voltage pulsed electrocoagulation techonology is an ideal using technique for the treatment to the electroplating wastewater containing chromium and zinc and has a great potential for industrial application.
What problem does this paper attempt to address?