Influence of leakage of natural non-azeotropic mixture refrigerants on performance of auto-cascade refrigeration cycle

Yan Gang,Wang Wei,Qian Wenbo,Feng Yongbin
DOI: https://doi.org/10.3969/j.issn.1009-8402.2009.02.005
2009-01-01
Abstract:Analyzes the influence of leakage in different parts which leads to the composition change of refrigerant based on the isothermal leakage of non-azeotropic refrigerant in two-phase area.Studies the leakage characteristics of different leakage points with different leakage ratio using natural refrigerants R600a/CO2.The results show that the refrigerant composition and performance of cycle both change when refrigerant leaks out.In particularly,the leakage at the outlet of evaporator plays the most important role in system performance.The adjusting ability in capacity and pressure ratio of compressor reduces obviously if the composition of refrigerant changes a lot due to the leakage,which also results to the unsatisfied requirement of working condition and worse system performance.