Study on leakage of mixture refrigerant in auto-cascade refrigeration cycle

Ren Nuoying,Yan Gang,Yan Jun,Wu Yezheng
DOI: https://doi.org/10.3969/j.issn.1001-7100.2007.01.018
2007-01-01
Abstract:Although auto-cascade refrigeration cycle was widely used in cryogenic and refrigerating field,there was less study related to the leakage characteristics of refrigerant in the cycle.The influence of leakage in each part of auto-cascade device on composition of refrigerant was analyzed based on the isothermal leakage of non-azeotropic refrigerant in two-phase area.The influence of leakage at exit of condenser,vapor-liquid separator and evaporator on the refrigerant composition is bigger.Taking the auto-cascade cryogenic compartment using non-azeotropic refrigerant R600a/CO2 for example,the leakage characteristics of different leakage point and ratio were studied.The results show that refrigerant composition and performance of cycle is changed when refrigerant leaks out.The influence of leakage at exit of evaporator is maximal. When composition of refrigerant changes much due to the leakage,the adjusting ability of capacity and pressure ratio of compressor reduces obviously.In the case,the system can not meet the requirement of working condition and the performance of cycle is worsen.
What problem does this paper attempt to address?