Performance Study on R600a/CO2 Auto-Cascade Refrigerating Cycle with One-Step Dephlegmation and Two-Step Dephlegmation

Jun Yan,Nuoying Ren,Wei Qian,Gang Yan,Yanzhong Li
DOI: https://doi.org/10.3321/j.issn:0253-987X.2007.03.013
2007-01-01
Abstract:Theoretical analyses on auto-cascade refrigerating cycle with one-step dephlegmation and two-step dephlegmation were performed to discuss the influence of composition, evaporating temperature, condensing temperature and supercooling on the system performance when using non-azeotropic mixture refrigerant R600a/CO2. The results show that each cycle has an optimal mixture composition ratio of the mixture refrigerant, and an optimal medium temperature exists in two-step dephlegmation cycle. Moreover, at the certain evaporating temperature and condensing temperature, coefficient of performance, refrigerating output by unit mass refrigerant and compression ratio of two-step dephlegmation cycle are greater than those of one-step dephlegmation cycle. When evaporating temperature and condensing temperature increase, the difference of performance between two-step dephlegmation cycle and one-step dephlegmation cycle is greater.
What problem does this paper attempt to address?