The theoretical performance analysis of the application of different mixed refrigerants for the auto-cascade refrigeration unit

Qian Wenbo,Yan Gang,Feng Yongbin,Wang Wei,Zhang Yingzhi
DOI: https://doi.org/10.3969/j.issn.1001-7100.2008.10.004
2008-01-01
Abstract:The different mixed refrigerants directly impact on the performances of the auto-cascade refrigeration unit.This article focused on the impact of both the mixed rate of refrigerant such as R744/R600a、R744/R290、R744/R134a、R23/R134a、R23/R22、R32/R600 and outlet temperature of the evaporator to the condensed pressure,the refrigeration capacity,compressor consumption and COP.It was concluded that the supreme mixed ratio of R744/R600a、R744/R290、R744/R134a、R32/R600a is 65∶35,R23/R134a is 60∶40 and R23/R22 is 70∶30.The system COP of R744/R290 is highest among them.With the increasement of the lower boiling point component,the refrigeration capacity and the compressor consumption of the R744/R290、R744/R134a、R23/R22 units go up first and then down later,however,those of R23/R134a 、R32/R600 、R744/R600a increase all the time;with the rise of the evaporation temperature in the case of the the supreme mixed ratio,the COP of the units continues to go up,whereas the condensed pressure is nearly constant.