Research and Application on One Time Through-Flow Test Methods of HVDC Converter Rheological

LI Peng,YUAN Yu-bo,ZHANG Jia-min,GAO Lei
DOI: https://doi.org/10.3969/j.issn.1009-0665.2012.06.007
2012-01-01
Abstract:It is a complicated and difficult job to make sure the polarity of the bushing current transformers(TA) and correctness of its secondary circuit in HVDC converter transformer protection debugging.Combined with practical engineering applications,the method that uses one time through-flow to check secondary circuit of converter transformer bushing TA with DC and AC is proposed in this paper.On the basis of the introduction about the side of the same name and polarity of transformer,the theory that uses one time through-flow to check secondary circuit of converter transformer bushing TA with DC and AC is analyzed,and the key problems and complete implementation on methods and site applications is given in this paper.Taking advantage of renovation debugging on the zhengping converter transformer protection,the method that uses one time through-flow to check secondary circuit of converter transformer bushing TA with DC and AC is applied to the practical work to check the correct and integrity of secondary current loop polarity and wiring.The effectiveness of this program is verified with starting the test with a load test in spot.