Abstract:A model 9 kVA (240 V/9.6 V) single-phase HTS transformer has been developed and tested with and without a cold iron core at 77 K. The primary and secondary windings were wound by transposed conductors, which are made from stainless steel-reinforced multifilamentary Bi2223/Ag tapes. The structures of the primary and secondary windings are helical and double-pancake, respectively. Primarily characteristics of the transformer are obtained through no-load tests, and short circuit tests. The iron cores are made of the common laminated Fe-Si steel plates and operate at nitrogen temperature 77 K. Based on the results of this transformer, we will develop a 630 kVA HTS transformer with the same rating currents in the near future.