Electromagnetic Field Analysis of Three Typical Incoming Lines in 220 kV GIS Substation

Mu Qiugu,Zhou Kai,Xiao Xianyong
DOI: https://doi.org/10.3969/j.issn.1003-6954.2011.05.007
2011-01-01
Abstract:The electromagnetic environment of high-voltage transmission systems has become the focus with the increase in high voltage transmission level.The distribution features of power-frequency electric field and magnetic field of three typical incoming lines in 220 kV GIS(gas-insulated switchgear) substation are investigated and analyzed.Firstly,the models of three typical incoming lines are established.Then the horizontal distribution of power-frequency electric field and magnetic field at the height of 1.5 meters and 15 meters above the ground is simulated and calculated using finite element method(FEM) with the software of COMSOL Multiphysics.Finally,according to ″Guidelines for Limiting Exposure To Time-varying Electric,Magnetic,and Electromagnetic Fields(up to 300 Hz)″(ICNRIP,1998),the data of simulation calculation is analyzed and evaluated.The result indicates that the power-frequency electromagnetic fields generated by three kinds of incoming lines in 220 kV GIS substation are lower than the public exposure limits prescribed in ICNRIP.
What problem does this paper attempt to address?