Design and Operation of Biofiltration Deodorization System in Municipal Wastewater Treatment Plant

Yan-fen QU,Jin-shao YE,Hua YIN
DOI: https://doi.org/10.3321/j.issn:1000-4602.2007.04.010
2007-01-01
Abstract:The biofiltration method was used to treat the odor produced from the activated sludge thickener and sludge dehydrating unit of a municipal wastewater treatment plant in southern China.The operation results for sixty days show that the concentrations of hydrogen sulfide and ammonia in the outflow are ranged from 0.01 mg/m3 to 0.08 mg/m3,and from 0 mg/m3 to 0.62 mg/m3 respectively when the concentrations of hydrogen sulfide and ammonia in the inflow are 0.18 mg/m3 to 2.71 mg/m3 and(1.93) mg/m3 to 5.95 mg/m3.The quality of the outflow can achieve the second discharge standard within a range of 6 m outside of the plant.The microbial species on the filter medium are dramatically abundant,especially the bacteria which are 0.3 × 109 CFU/g to 5.4 × 109 CFU/g.And the dominant genera are Bacillus,Pseudomonas,Thiobacillus,Saccharomyces,Candida,Aspergillus and Penicillium.