Analysis and Treatment for Generator TV Terminal Third Harmonic

LIU Yi-dan,YUAN Yu-bo,ZHANG Liang,LI Zi-bin,WANG Hong-xing
DOI: https://doi.org/10.3969/j.issn.1009-0665.2006.01.015
2006-01-01
Abstract:The third harmonic voltage of generator terminal TV is measured during the electric commissioning of first gas turbine of Zhangjiagang Huaxing Power Plant.The reason for third harmonic voltage producing by recording wave is analyzed and treated.Simulating the neutral winding grounded and non-grounded with MATLAB could verify that the third harmonic voltage of TV second winding is reduced if the third harmonic of excitation current can flow out.So the non-linear resistance is connected on the triangular winding,at the same time it is suggested that the generator terminal TV of Huaxing Power Plant should be configured triangular windings.
What problem does this paper attempt to address?