A Kind of Three-phase Locked Loop for Harmonic Detection

ZHANG Wenlong,CHEN Yongqiang,QIU Xiaochu
2013-01-01
Abstract:The test method of instantaneous reactive power theory(iP-iQ) is insufficient in harmonic detection under grid voltage imbalance and distortion.In order to accurately detect the load harmonic current,we propose a novel three-phase locked loop which is based on double synchronous coordinate transform and cross decoupling to eliminate double frequency component,improve the precision of phase locking and effectively eliminate the ripple.Compared with harmonic detection simulation result of traditional phase locked loop(SRF-PLL) used in iP-iQ method,the novel phase locked loop(IDDSRF-PLL) makes the fundamental current distortion rate reduced by 1.18% in grid voltage imbalance and 1.42% in grid voltage distortion.Thus,the novel method can improve the detection performance to some extent.