An UPS Inverter Output Phase Control Strategy

ZHANG An-yang,DONG De-zhi,CHEN Min,XU De-hong
DOI: https://doi.org/10.13234/j.issn.2095-2805.2013.3.31
2013-01-01
Abstract:The synchronization of the UPS output and the grid is an important indicator to measure the UPS. An UPS inverter output phase feedback control strategy was studied, which could obtain the grid phase by software phase-locked loop to become the phase reference of the inverter output phase. Then the feedback control was used so that the inverter output phase could track the reference phase precisely. Based on theoretical analysis, a compensation network of output phase feedback control was designed. The control method was verified on the three-level UPS inverter platform, the experimental results show that the inverter output is able to synchronize with the grid through this method.