Studies on Corona Rings for UHV Lines Insulator Strings based on Electrical Network Method

赵丹丹,郭洁,文远芳,余芳
DOI: https://doi.org/10.16188/j.isa.1003-8337.2008.04.004
2008-01-01
Abstract:The first two insulator units at line end of UHV insulator string without corona rings bear extremely uneven voltage stress of about 14.4%and 11.1% respectively. The size and cover depth of corona rings of UHV suspension porcelain insulator stings were calculated by electric-network method. The results showed that for a better voltage distribution, the stray capacitance between corona ring and insulators should be large enough within limit of 33 F to obtain best distribution, which appeared when corona rings were installed at 3-unit-long cover depth at both ends of insulator string. It is suggested that triangle cup tower should be chose in engineering practice to minimize unconsistency of voltage distribution between string of 3 phases.
What problem does this paper attempt to address?