Corona Characteristic Research of Suspension String Fittings for High Altitude 330 kV Transmission Line
梁进祥,鄂士平,全姗姗,彭宗仁,曹晶
2017-01-01
Abstract:In some high altitude northwest area of China,corona discharge phenomenon of fittings is obvious for suspension ring of 330 kV double-circuit transmission line.In order to reduce power loss,three-dimensional finite element analysis method was used to model double-loop transmission line in the same tower and calculate surface electric field distribution of suspension string.According to calculation result,corona discharge research work is performed both at climate laboratory in Ultra-high Voltage AC Test Base and Ultra-high Voltage AC Test Field.It indicates that the intensity of fittings is decreased by nearly 20.8% to 22.4 kV/cm from 28.3 kV/cm by installation of anti-corona ball,and the inception and extinction voltage after optimization is respectively 12.6%,5.6% higher than before.Corona discharge voltage decreases with the rise of altitude above the sea level,and discharge voltage at 4 300 m is approximately 31.00%,31.1 % lower than 0 m.Thus,it can be taken as a reference during the design and optimization for transmission project at high altitude area.