Computational Analysis on Voltage Distribution along Ceramic Insulator Strings of UHV AC Transmission Line

陈林华,梁曦东
2012-01-01
Abstract:The voltage distribution along the long insulator strings of UHV AC transmission lines is very non-uniform,so it is necessary to research the voltage distribution.Using the combination of the charge simulation method(CSM) and the boundary element method(BEM),we respectively calculated the stray capacitance between every ceramic insulator and towers or lines,and applied these results to construct a chain circuit.Then we efficiently calculated and analyzed the voltage distribution along the insulator strings of the AC 1 000 kV transmission lines under dry and wet conditions.The calculated results show that the self-capacitance of the insulator has a slight effect on the voltage distribution,and using grading rings is the main measure to control the voltage distribution;the surface condition of the insulator has little effect on the voltage distribution when the insulator resistance is over 300 MΩ and the increase in the leakage electric conductance within certain range can improve the uniformity of the voltage distribution;if the semiconducting glaze insulator is used,the resistance of each insulator should be about 10~20 MΩ;the faulty insulator will aggravate the uniformity of the voltage distribution and the maximum voltage drop across the insulator may be over 30 kV when the faulty insulator is nearby the line.