Voltage-Sharing Characteristics of II-Shaped Tension Ceramic Insulator String with Jumpers in UHVAC Substation

程建伟
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.09.004
2012-01-01
Abstract:Ceramic cap and pin insulators are used in the substations of 1000 kV UHVAC pilot project.Due to the high voltage level,complex tower,insulator strings,and different conductor arrangement,the interactions between insulator strings in different position and phase lead to the uneven voltage distribution at high voltage side and along the insulator strings.Consequently,with three-dimensional finite element method,considering the influences of the tower and jumper and the interaction of the three phases,we calculated the potential and electric field distribution of the V-type strain insulator strings with jumper in 1000 kV substation,studied the influence of grading ring to the voltage-sharing characteristics of the insulator strings,and optimized the parameters of the grading ring.Moreover,we suggested the proper configuration of the grading ring.The research achievements can improve the reliability of the insulators in 1000 kV substations and have been successfully applied to the UHVAC pilot project.
What problem does this paper attempt to address?