Abstract:It is becoming more difficult to distinguish fault current which is through high impedance and the current when train starts. The principle of current increment protection and current slope-change protection was discussed, and a new method named as DC admittance protection, which based on the method mentioned above, was put forward. The criterion of DC admittance slope-change protection and DC admittance increment protection details, the method of how to set the setting value were presented. The experiment results show that the DC admittance protection can detect the short circuit fault more selectively. The microcomputer based feeder proposed protection scheme was developed.