FIRE PROTECTIVE COATING OF CONCRETE-FILLED SQUARE HOLLOW SECTIONS BEING EXPOSED TO THREE-SIDE FIRE

Yang Hua,Zhang Sumei
DOI: https://doi.org/10.3969/j.issn.1007-9963.2013.10.018
2013-01-01
Steel Construction
Abstract:CFST columns may be exposed to three-side fire when they are subjected to an actual fire.The decrease of fire exposure boundaries leads to generally lower cross-sectional temperature,thus inducing an unsymmetrical temperature distribution and additional load eccentricity,which causes fire resistance behaviors differing from fourside fire condition.A series of parametric analysis was carried out for the fire resistance of the columns in three-side fire,in which thickness of fire-proof coating,load ratio,cross-sectional depth,slenderness ratio and load eccentricity ratio were taken into account.The analysis results indicate that the load ratio,sectional width and slenderness ratio are the main parameters that influence the fire resistance of concrete filled SHS columns.The influence of the loading eccentricity is also obvious when load location leaning to the unexposed side.Hereafter a set of design tables in which minimum thickness of fire-proof coating may be determined,and the tables may provide references for fire design of those concrete-filled SHS being exposed to three-side fire in construction application.