Study on Quota Heating under Fault Condition of Ring-shaped Heat-supply Network

Xiao-xia WANG,Ping-hua ZOU
DOI: https://doi.org/10.3969/j.issn.1000-4416.2006.06.017
2006-01-01
Abstract:The mathematical model of hydraulic regime of ring-shaped heat-supply network is established,and the pressure head check formula for quota heating is given.Taking a ring-shaped heat-supply network for example,when non-quota heating is used due to fault of a pipeline section,the flow rate obtained by heat users being away from heat source is too small to satisfy the lowest heating requirement;when quota heating is used,the heating balance of all heat users can be attained.The pressure diagrams of normal condition and quota heating condition are compared.The quota heating should be used when a fault takes place at the main of ring-shaped heat-supply network.