Numerical Simulation of Fluctuating Wind Load and Wind-Induced Response of Large Hyperbolic Cooling Tower

鲍侃袁,沈国辉,孙炳楠
DOI: https://doi.org/10.3785/j.issn.1008-973x.2010.05.020
2009-01-01
Abstract:An auto-regressive (AR) linear filter method was used to simulate the spatial correlative multiple fluctuating wind load on the outside surface of cooling tower. The characteristic of simulation results was analyzed with the time domain and the frequency domain method. Results indicate that quasi-steady theory is not appropriate. The distribution of natural frequency and the mode characteristic were calculated through the finite element method. The natural frequencies were densely distributed,and first 40 of them were confined to 1.0~2.2 Hz. The transient analysis was conducted under the fluctuating wind load. Then the various responses of cooling tower in time domain and frequency domain were achieved. The background and the resonant parts were studied respectively,and the appropriate sampling interval was discussed. Transient dynamic analysis results show that the wind induced displacement reaches maximum at someplace close to neck and Mises stress reaches maximum at someplace near the bottom.
What problem does this paper attempt to address?